|
Specification Writing Notes
(.rtf)
Product Guide Specification
(.rtf)
Specification Writing Notes
BioBased Insulation System
The following notes related to 07218 - Semirigid Polyurethane Spray Insulation
is intended to aid the specification writer in preparing a coordinated
set of construction specifications. The specification writer should take
specific project conditions into consideration when implementing any of
the notes. Consult your local representative for assistance when editing
the section.
1. Limitations on Use of Materials:
BioBased insulation shall not be installed on the exterior of the building
below grade, in contact with water, in service environments above 180oF (82oC)
above roofing membranes, within two (2) inches (50 mm) of heat emitting devices
where the temperature is in excess of 200oF (93oC) or as an interior finish.
2. Wood framed construction
In the Carpentry section of Division 6 Wood and Plastics specify the following
requirements:
A. All new foundation sill plates and floor/wall junction plates shall be installed
with foam gaskets to prevent air leakage or specify the caulking of these joints
on the interior of the building in the joint sealant section of the specifications.
B. All rough size openings for new exterior doors and windows shall be sized
to furnish a minimum ½ inch (12.5 mm) space around the perimeter of
the door and/or window frame to permit the installation of the foam insulation.
3. Thermal and Moisture Protection
In the appropriate section of Division 7 Thermal and Moisture Protection, specify
the following requirements:
A. Caulk all joints between adjacent exterior framing members, between multiple
studs and at other critical locations where the installation of insulation
is not possible.
Specifier Notes: Use of a vapor retarder or vapor barrier is normally not considered
part of the BioBased Insulation System except in wet locations such as pool
rooms. Sections ‘b’ and ‘c’ below are included for
code compliance in jurisdictions that require use of a vapor barrier. Preferred
practice does not include a vapor barrier since over 99% of moisture travel
is blocked by BioBased resistance to air movement.
B. Vapor retarder shall be installed if required by system design or regional
building codes.
C. Vapor retarder, if used on ceilings, shall be caulked and stapled to the
top plates of interior partitions and to the lower top plates of exterior walls.
4. Finishes
In the appropriate section of Division 9 Finishes, specify the following requirements:
Specifier Notes: All class 1 insulation products are required by code to be
separated from living area by a 15 minute thermal barrier.
A. Insulation shall be separated from the interior of the building by 1/2" (12.7
mm) gypsum board or equivalent approved 15 minute thermal barrier.
B. Cavity fill application holes made through interior/exterior finishes shall
be repaired.
5. Plumbing
In the appropriate plumbing section of Division 15 Mechanical, specify the
following requirements:
A. All cleanouts and valves shall be identified in order to avoid the installation
of insulation at these locations.
B. All plumbing stacks which penetrate the exterior walls and/or ceilings shall
be cut in so as to provide a minimum ½ inch (12.5 mm) space around the
stack to permit the installation of insulation.
C. All PVC or ABS pipe of three (3) inches (75 mm) or less in diameter must
be braced every three (3) feet (1 m) to prevent excessive deflection by the
expanding foam.
6. Ventilation
In the appropriate section of Division 15 Mechanical, specify the following
requirements:
A. All damper controls shall be identified in order to avoid the installation
of insulation at these locations.
B. All combustion appliances shall either be provided with a venting relief
safety switch or be uncoupled from the building envelope such that pressure
imbalances across the envelope do not interfere with combustion and/or make-up
air supply to the combustion chamber.
C. The building shall be designed with adequate mechanical ventilation to meet
the requirements of the local governing codes.
D. The heating and ventilation system shall be properly designed and balanced
to prevent back draft of combustion appliances and to achieve adequate air
changes.
7. Electrical
In the appropriate section of Division 16 Electrical, specify the following
requirements:
A. All new vertical wiring shall be secured to the inside of studs every three
(3) feet (1 m).
B. In retrofit applications, all existing wiring that is not to be abandoned
shall not to be insulated over in accordance with applicable electrical codes.
C. All ceiling fixtures shall be installed using vapor barrier pans or boxes
which are caulked with acoustical caulking material, or, all ceiling fixtures
shall be sealed using a suitable sprayed foam material prior to the installation
of attic insulation.
D. All wiring systems such as cable TV, telephone, security systems and intercoms
shall be mechanically fastened to the inside of studs every three (3) feet
(1 m) for vertical runs, and 1-1/2 inches (40 mm) from the gypsum board surface
for all runs.
|